Interpreting Winding Insulation Power Factor Test Results

  • July 2013
  • Number of views: 5494
  • Article rating: No rating

Vicki Warren, Iris Power
Mississauga, Ontario
Brian F. Moore, Georgia Power
Atlanta, Georgia

Surveys have shown that stator winding insulation failure account for about 40% of motor failures in motors rated 2300V and above. In addition, the work force in general is losing its technical experience. This impacts both the customers we serve and our own internal work force that fixes the equipment.  Lastly, there seems to be a shift toward a more political type customer base that is less likely to own up to their contribution to motor failures. These reasons combine to force motor shops into better testing to know that a more reliable product is being shipped.

Several old and new test methods have recently gained popularity with AC induction motor maintenance specialists.  This paper, presented at the 2013 EASA Convention, will examine Power Factor Tip-up and Partial discharge testing to assess stator winding conditions for motors rated 2300V and above. Both tests will be evaluated for: effectiveness; which windings/types of machines the test is effective; set-up; interpretation and limitations.

Topics discussed include:

  • Brief review of stator winding failure mechanisms
  • Brief review of power factor and power factor tip-up
    • The theory/math behind it
    • Georgia Power’s use as a sorting tool
  • Partial discharge terms that apply to power factor and tip-up testing
    •   Inception and extinction voltage
    •   Magnitude
    •   Polarity
  • Reading actual power factor and test data sheets
    •   Advantages and limitations of off-line tests
    •   Deciding if there is a problem or not
  • Case studies: What to do next (if you suspect a problem)
    • Partial discharge testing (brief theory and expected results)
    • Dynamometer testing or full-load testing at the customer’s plant us

LOGIN TO DOWNLOAD THE PAPER



Rate this article:
No rating
Print


PREVIOUS ITEM
Comments are only visible to subscribers.

Getting The Most From Your Electric Motors

Getting The Most From Your Electric Motors - coverThis 40-page booklet provides great advice for obtaining the longest, most efficient and cost-effective operation from general and definite purpose electric motors.

This booklet covers topics such as:

  • Installation, startup and baseline information
  • Operational monitoring and maintenance
  • Motor and baseline installation data
  • How to read a motor nameplate
  • Motor storage recommendations

LEARN MORE AND DOWNLOAD MÁS INFORMACIÓN Y DESCARGAR BUY PRINTED COPIES

READ MORE ABOUT THE FEATURES AND BENEFITS

EASA/AEMT Rewind Study

EASA Rewind Study cover

The Effect of Repair/Rewinding on Premium Efficiency/IE3 Motors
Tests prove Premium Efficiency/IE3 Motors can be rewound without degrading efficiency.

DOWNLOAD THE FULL RESULTS

ANSI/EASA AR100-2020

ANSI/EASA AR100-2015 cover

Recommended Practice for the Repair of Rotating Electrical Apparatus
This is a must-have guide to the repair of rotating electrical machines. Its purpose is to establish recommended practices in each step of the rotating electrical apparatus rewinding and rebuilding processes.

DOWNLOAD - ENGLISH

DESCARGAR - ESPAÑOL

EASA Technical Manual

EASA Technical Manual cover

Revised May 2024
The EASA Technical Manual is the association's definitive and most complete publication. It's available FREE to members in an online format. Members can also download PDFs of the entire manual or individual sections.

VIEW & DOWNLOAD