Article

What does it mean when a rewound motor runs "hot"? Items to check to make sure it's operating properly

  • July 2008
  • Number of views: 4366
  • Article rating: No rating

“We have rewound a motor, and now that it is back in service, our cus­tomer says it’s running hot. The frame is getting so hot that he can’t put his hand on it, and now he is blaming us for rewinding the motor incorrectly!” 

Has this ever happened to you? You have rewound a motor without changing the design at all; you tested the motor before you sent it out, and everything appeared to be fine. But now your customer wants you to fig­ure out what is wrong, or rewind the motor again. 

Before you consider this, there are a few things to check to see if the motor is, in fact, running properly. It is quite possible that the motor ran “hot” before it failed, but what are the chances that someone on-site put their hand to the frame before it had to be rewound? 

You can’t tell by frame temperature 
There is not a way to determine the winding temperature of a motor just by feeling the frame. The maximum tem­perature rating, based on the class of insulation, applies to the winding temperature at the hottest spot inside the motor. The temperature of the frame can be between 20° C and 40° C (or less, or more) cooler, depending on the design of the frame and the enclosure. 

Insulation class 
The insulation class of a winding is determined by the maximum tempera­ture it can withstand before complete breakdown. The majority of motors manufactured today use a Class F (155° C) or Class H (180° C) system. Many service centers will use a Class H system on all rewinds. Assuming that the ambient temperature is 40° C, NEMA states that at 1.0 service factor, the maximum winding temperature rise for a Class F system is 105° C. Note: It is very important to remember that even though the insulation system may be able to withstand very high temperatures, for every 10° C rise in total winding temperature, the insula­tion life will be cut in half. 

Example 
This example will illustrate that the motor frame can be quite hot even if it is running perfectly fine. Let’s assume that a particular motor is wound with Class F insulation and has a 40° C ambient temperature. Let’s also assume that this motor is a high efficiency design that operates with a Class B temperature rise (80° C winding temperature rise). At full load, we can assume that the total wind­ing temperature is somewhere around 120° C, well below the design limit for the Class F insulation. If we estimate that the frame temperature is 40° C lower than the winding temperature (pretty liberal), then that means the frame is going to be about 80° C on the surface. 80° C equals 176° F, and I don’t know about you, but I certainly couldn’t hold my hand on a frame that hot for any length of time! 

Check the amps! 
The best way to determine if the motor is running properly is to check the current draw with an ammeter.  If the current is less than or equal to the nameplate current, then you are probably not overheating the mo­tor. If the current is higher than the nameplate reading, then it is possible that the motor is running too hot. Overloading, high or low voltage, restricted ventilation, or high ambient are the most common causes of motor overheating. 

Older motors 
In general, the old NEMA U-frame motors ran cooler than today’s T-frames, mainly because the insulation systems were of lower temperature rating such as Class A (105° C ). If a U-frame motor is replaced with a T-frame, it may be alarming to your customer that it runs much hotter, when actually it may be running even more efficiently than the old one. 

Explosion-proof motors 
There is one case where it is very important that the frame surface temperature be kept somewhat cool. An explosion-proof motor requires that the surface temperature be below the ignition point of the hazardous material in the environment. Some of these motors come equipped with temperature sensors that will trip the motor offline when the winding tem­perature exceeds a certain level. UL sets the standard temperatures based on the gas, vapor, or dust present in the environment. However, there is no standard for other general purpose motors. 

The best way to determine whether a motor is running within a safe oper­ating temperature is to use temperature sensors, like thermostats or RTD’s to monitor the winding temperature. As mentioned before, you can also mon­itor the current to get a basic idea of how the motor is running. But do not rely solely on the frame surface temperature because it is in no way an accurate method to determine the “safe” operating temperature. 



Print


PREVIOUS ITEM

Getting The Most From Your Electric Motors

Getting The Most From Your Electric Motors - coverThis 40-page booklet provides great advice for obtaining the longest, most efficient and cost-effective operation from general and definite purpose electric motors.

This booklet covers topics such as:

  • Installation, startup and baseline information
  • Operational monitoring and maintenance
  • Motor and baseline installation data
  • How to read a motor nameplate
  • Motor storage recommendations

LEARN MORE AND DOWNLOAD MÁS INFORMACIÓN Y DESCARGAR BUY PRINTED COPIES

READ MORE ABOUT THE FEATURES AND BENEFITS

EASA/AEMT Rewind Study

EASA Rewind Study cover

The Effect of Repair/Rewinding on Premium Efficiency/IE3 Motors
Tests prove Premium Efficiency/IE3 Motors can be rewound without degrading efficiency.

DOWNLOAD THE FULL RESULTS

ANSI/EASA AR100-2020

ANSI/EASA AR100-2015 cover

Recommended Practice for the Repair of Rotating Electrical Apparatus
This is a must-have guide to the repair of rotating electrical machines. Its purpose is to establish recommended practices in each step of the rotating electrical apparatus rewinding and rebuilding processes.

DOWNLOAD - ENGLISH

DESCARGAR - ESPAÑOL

EASA Technical Manual

EASA Technical Manual cover

Revised May 2024
The EASA Technical Manual is the association's definitive and most complete publication. It's available FREE to members in an online format. Members can also download PDFs of the entire manual or individual sections.

VIEW & DOWNLOAD