In the April 2007 issue of CURRENTS, we covered surge testing anomalies, speci.cally for AC windings. The surge test can be used for DC windings as well. It can be a useful tool for evaluating armatures and some DC fields.
A note of caution: If a winding does not have a minimum insulation resistance per ANSI/EASA AR100-2006, it is not safe to apply an overpotential test (surge or high potential).
Surge testing shunt .elds may not provide meaningful results if the surge pulse decays too quickly — if it dissipates through only the .rst few hundred turns. To obtain a test voltage high enough to test every turn would require too high a voltage. That high voltage would overstress the ground-wall insulation.