Article

Use polarization index test to determine condition/health of motor insulation

  • September 2000
  • Number of views: 8553
  • Article rating: 1.0

Chuck Yung
EASA Technical Support Specialist

Insulation resistance is affected by several variables: the type of insulation, age of the material, surface area, moisture and contamination. Insulation resistance can be described as being made up of four components: Leakage, capacitance, conduction and absorption. Capacitance normally only affects the first few seconds of the Polarization Index (PI) test; conduction should be essentially zero if the windings are dry; and leakage current is constant over time.

The PI test is useful because the remaining variable – absorption current – indicates the health of the insulation.

The PI test is used to determine the condition of motor insulation to ground. The ratio of 1-minute to 10-minute resistance is recorded.

10 minute resistance / 1-minute resistance = PI ratio

The PI measures the time required for molecules of insulation to polarize to resist the flow of current. Insulation molecules at rest are randomly oriented (see Figure, top). When current is applied to the windings, the molecules align themselves (see Figure, bottom) to resist the flow of current. How quickly this happens tells us a lot about the condition of the insulation.

Image

Because the PI measures insulation resistance between the conductors and ground, this test is only useful for taped/sealed coils. The purpose of the PI test is to gauge the condition of the insulation, so a large amount of conductor surface exposed to air (air is an insulator) skews the results. Humidity and surface contamination would greatly affect the values obtained. That makes the PI test ineffective for random windings, most fields and any winding with “appreciable amounts of exposed conductors.”
 
The ratio should be between 2 and 5, normally. A ratio below 2 indicates a dirty or moist winding. A ratio above 5 may indicate a very dry, brittle insulation system. There are exceptions
to the above guidelines. High- voltage VPI and pressed-coil insulation systems may yield a PI between 1 and 2, for a perfectly good winding. Newer epoxy insulation systems have such a fast reaction time that the molecules polarize almost insantly.

According to IEEE 43-2000, when the “1-minute insulation resistance is over 5000 meg-ohms, the calculated PI may not be meaningful.”

When a winding is energized by megger or hipot or in service – the insulation molecules polarize.

Image

Because it takes time for the insulation molecules to return to their “at rest” position, the windings must be de-energized long enough to return to rest. If the molecules are not fully at rest, it will take less time for them to polarize and the PI ratio will be misleading. Megging a motor before the PI test will artificially lower the PI ratio.

To ensure a valid PI test, ground the motor leads to the frame for 20-30+ minutes before doing the PI test. Doing a PI test immediately after the windings are energized for any reason will skew the results of the PI test.



Print


PREVIOUS ITEM

Getting The Most From Your Electric Motors

Getting The Most From Your Electric Motors - coverThis 40-page booklet provides great advice for obtaining the longest, most efficient and cost-effective operation from general and definite purpose electric motors.

This booklet covers topics such as:

  • Installation, startup and baseline information
  • Operational monitoring and maintenance
  • Motor and baseline installation data
  • How to read a motor nameplate
  • Motor storage recommendations

LEARN MORE AND DOWNLOAD MÁS INFORMACIÓN Y DESCARGAR BUY PRINTED COPIES

READ MORE ABOUT THE FEATURES AND BENEFITS

EASA/AEMT Rewind Study

EASA Rewind Study cover

The Effect of Repair/Rewinding on Premium Efficiency/IE3 Motors
Tests prove Premium Efficiency/IE3 Motors can be rewound without degrading efficiency.

DOWNLOAD THE FULL RESULTS

ANSI/EASA AR100-2020

ANSI/EASA AR100-2015 cover

Recommended Practice for the Repair of Rotating Electrical Apparatus
This is a must-have guide to the repair of rotating electrical machines. Its purpose is to establish recommended practices in each step of the rotating electrical apparatus rewinding and rebuilding processes.

DOWNLOAD - ENGLISH

DESCARGAR - ESPAÑOL

EASA Technical Manual

EASA Technical Manual cover

Revised May 2024
The EASA Technical Manual is the association's definitive and most complete publication. It's available FREE to members in an online format. Members can also download PDFs of the entire manual or individual sections.

VIEW & DOWNLOAD