The effects of high or low voltage on the performance of a motor

  • August 2000
  • Number of views: 4812
  • Article rating: 4.0

Cyndi Nyberg 
Former EASA Technical Support Specialist 

NEMA MG-1-12.45 states that motors shall operate successfully under running conditions at rated load with a variation in the voltage or the frequency up to the following: 

  • Plus or minus 10 percent of rated voltage, with rated frequency. 
  • Plus or minus 5 percent of rated frequency, with rated voltage. 
  • A combined variation in voltage and frequency of 10 percent (sum of total values) of the rated values, provided the frequency variation does not exceed plus or minus 5 percent of rated frequency. 

There is usually no problem with frequency variation, unless we get into operating at 50 Hz, but that would be an article all by itself, so the focus here will be on voltage variation only. Even though NEMA states that motors are designed to operate within 10 percent of rated voltage, that doesn’t give an accurate picture of what will happen when a motor is operated with high or low voltage. Any change from the rated voltage and frequency will affect the performance of the motor, sometimes dramatically.

Today’s standard T-frame motors are designed with high flux densities and therefore are more susceptible to improper voltage conditions that will affect performance.

Older motors and high-efficiency motors are designed with lower flux densities, so any variation from the rated voltage will no affect the performance as much (but it may still have negative effects!)

Image

 
Higher voltage equals higher flux, so in some situations, high voltage can actually improve the performance, but at some point the core will begin to saturate and heat up quickly.

Having a low voltage supply is more danger- ous than high voltage, because as less voltage is applied, there is less flux in the iron. Less flux means the core iron is not being used to its optimal level, so efficiency and torque start to fall.

More often than not, your customer will have a high voltage supply, but there are cases where it may be low. For example, you could have a motor designed for 440v, but the power supply is actually 485v or 490v, which is right on the edge of 10 percent over voltage. Or you could have a motor designed for 230v, and the power supply is only 208v, right on the edge of 10 percent under voltage.

The following is a summary of the effects of over and under voltage for typical induction motors:

Torque
The torque of an induction motor varies as the square of the voltage, so any small variation in voltage will significantly affect the starting and maximum torque. At 110 percent voltage, torque will increase by 21 percent, but at 90 percent voltage, the torque will decrease by 19 percent. This could be a problem if the motor needs to start a high inertia load.

Speed
The speed of a motor is going to change slightly with high or low voltage. At 110 percent voltage, the speed will increase about 1 percent, and at 90 percent voltage it will decrease about 1.5 percent. But when you look at the speed change in percent slip, the numbers are more dramatic. At 110 percent voltage, the percent slip will decrease by 17 percent, but at 90 percent voltage, the slip will increase by 23 percent.

Efficiency
At 110 percent voltage, the efficiency of a motor may actually increase up to 1 percent. However, at 90 percent voltage, the efficiency is going to decrease about 2 percent. This will especially be a factor to consider for larger motors because of the cost of a lower efficiency.

Current
The starting and full load current will also be affected by changes in voltage. At 110 percent voltage, the starting current will go up 10-12 percent, but the full load current will go down 7 percent. This would be a problem if the power supply cannot handle the higher starting current. At 90 percent voltage, the starting current will decrease 10-12 percent, while the full load current will increase 11 percent.

Temperature rise
The temperature rise at full load will be some- what affected by variations in voltage. At 110 percent voltage, the temperature rise will decrease 3-40C, unless the core has become saturated (the temperature would increase). At 90 percent voltage, the temperature rise is going to increase 6- 70C. A general rule is that for every 100C increase in total temperature rise, the insulation life will be cut in half. Even a slight under-voltage is going to increase the temperature, so that can make a difference in the insulation life of the motor.

Overload capacity
At 110 percent voltage, the motor will actually have a 21 percent higher overload capacity, but at 90 percent, the capacity will decrease by 19 percent. More often than not, a motor is going to be overloaded for some period of time, so if the motor is operating with under-voltage, the possibility of failure increases.



Print


PREVIOUS ITEM

Getting The Most From Your Electric Motors

Getting The Most From Your Electric Motors - coverThis 40-page booklet provides great advice for obtaining the longest, most efficient and cost-effective operation from general and definite purpose electric motors.

This booklet covers topics such as:

  • Installation, startup and baseline information
  • Operational monitoring and maintenance
  • Motor and baseline installation data
  • How to read a motor nameplate
  • Motor storage recommendations

LEARN MORE AND DOWNLOAD MÁS INFORMACIÓN Y DESCARGAR BUY PRINTED COPIES

READ MORE ABOUT THE FEATURES AND BENEFITS

EASA/AEMT Rewind Study

EASA Rewind Study cover

The Effect of Repair/Rewinding on Premium Efficiency/IE3 Motors
Tests prove Premium Efficiency/IE3 Motors can be rewound without degrading efficiency.

DOWNLOAD THE FULL RESULTS

ANSI/EASA AR100-2020

ANSI/EASA AR100-2015 cover

Recommended Practice for the Repair of Rotating Electrical Apparatus
This is a must-have guide to the repair of rotating electrical machines. Its purpose is to establish recommended practices in each step of the rotating electrical apparatus rewinding and rebuilding processes.

DOWNLOAD - ENGLISH

DESCARGAR - ESPAÑOL

EASA Technical Manual

EASA Technical Manual cover

Revised May 2024
The EASA Technical Manual is the association's definitive and most complete publication. It's available FREE to members in an online format. Members can also download PDFs of the entire manual or individual sections.

VIEW & DOWNLOAD