Induction motor application guidelines for AC variable frequency drives

  • April 2015
  • Number of views: 5492
  • Article rating: No rating

Art Godfrey (retired)
Birclar Electric & Electronics
Romulus, Michigan

Introduction
Modern variable frequency drives (VFDs) offer an almost dizzying range of capabilities that include output fre­quencies into the hundreds of hertz. It can be tempting to use a standard AC induction motor with one of these VFDs. But doing so requires a thorough understanding of the intended applica­tion and how the VFD will affect the motor. Since the most popular VFDs sold today are pulse-width modulated (PWM) type, the comments and recom­mendations in this article will assume that is the type used.  Also, motor volt­age will be 600 volts or less.

Those who have been around for a few decades remember the first mo­tor problems associated with PWM VFDs; that is, winding failures. The lesson learned was that magnet wire insulation needed to be improved to withstand the higher peak voltages that resulted from many PWM VFD appli­cations. This was a somewhat painful time with finger-pointing between the drive and motor manufacturers, if they were different companies. 

Another problem this author wit­nessed, at the time working for one of the major motor manufacturers, was excessive rotor heating — enough to roast the stator winding insulation. In that case, the effect of the PWM drive was to crowd all the rotor bar current into the small upper section of the cast-aluminum rotor bars, closer to the rotor surface.

The next problem to surface was bearing failures attributable to shaft currents. Damage to bearings from shaft currents, especially from PWM inverters, has been well-documented. Research into the topic, which is exten­sive enough to warrant its own article, will show measures recommended to minimize the causes by using spe­cial cabling and specific grounding methods. The installation instructions from inverter manufacturers typically include specific wiring details. These include use of cable very different from common building wire, which also apply to the grounding from the motor back to the drive. One will also see methods of channeling the currents through shaft-grounding methods to provide paths other than the bearings of either the motor or driven equip­ment. Finally, insulating one or both bearings may be suggested since these will be the point of damage and even­tual cause of a shutdown.  

Discussion of the motor selection for use with the VFD can be split by speed:  less than or equal to “normal-power” synchronous speeds or above those synchronous speeds.  

Speeds less than or equal to nameplate speed
The first motor type that may be considered is a motor built to NEMA MG1 Part 30, a general purpose motor used on a sinusoidal bus (hereafter a standard motor). A starting point could be to gain assurance the manufacturer used inverter-duty magnet wire and other insulation system components suitable for VFD power. The next con­sideration is motor cooling, since it is well understood the rotor fins or shaft-mounted external fan will provide less cooling as speed is decreased.  With an understanding of the application load – the amount of torque at various speeds – one can reference manufacturer data similar to Table 1.  Note these assume starting with a 1.15 service factor motor and de-rating to 1.0.

Image

If a non-inverter motor is deemed suitable, modifications such as a shaft grounding brush and insulated bearing(s) provide insurance for a successful application. Drive manufac­turer wiring instructions may suggest more than typical grounding capabil­ity, such as a drilled and tapped frame ground. Also, a standard induction motor may have a resonant response when operated continuously at less than nameplate-rated speed. One can­not assume the manufacturer-included provision for continuous operation at less than rated speed in their design or testing.

Therefore, this possibility may be known only by test-running using VFD-power throughout the intended speed range. This author encountered several examples of this condition; the most significant entailed replacement of a 500 frame 6-pole with an 8-pole design. This concern is often seen with vertical motor applications due to the relative freedom of motion of the upper end. More detail is included in “Other considerations,” later in this article.

In sizing the VFD and motor, one needs to know starting torque re­quired. Generally, the VFD will limit torque available for break-away, re­gardless of the motor’s across-the-line capability.

Speeds greater than or equal to nameplate speed
If a standard will be consid­ered, one should have assurance its design is capable of continuous opera­tion above normal rated speed. Some generally smaller size standard motors may be designed for continuous me­chanical operation above rated speed, according to NEMA standards. How­ever, larger sizes cannot be assumed to have over-speed capability. For instance, a 10 hp NEMA Design B drip-proof 2-pole motor should be capable of 5400 rpm, but a similar 75 hp has no such capability. If the above examples are 4-pole, the maximum continuous speeds are 3600 for the 10 hp and 2700 rpm for the 75 hp.  (Data from NEMA MG1-12.52, Table 12-6.) NEMA stan­dards should be checked for any new motor considered for operation above nameplate speed.

If possible, check with the manufacturer. In terms of torque, the best one can hope for is constant power above rated speed, but de-rating will be required for speeds much above original rated speed. To know specifics about the torque capability, one should consult a qualified design expert. An­other serious consideration should be determining critical speed of the rotor/shaft assembly, including any shaft at­tachment such as a coupling.  

Given the above discussion, a cus­tom design may be more appropriate. What will or should end up being in­cluded in the motor design (and cost) are the following:

  • Power capability throughout the speed range that meets or exceeds application requirements.
  • Top speed that meets the applica­tion need.
  • Critical speed above maximum speed. The manufacturer should provide maximum overhung weight of shaft attachment that can be used up to that maximum speed.
  • Rotor and/or stator skew designs to minimize motor noise.
  • Rotor construction capable of centrifugal forces encountered running to top speed.
  • Design and construction that mini­mizes the possibility of resonant speeds within the operating range.

With the above comprehensive considerations, the manufacturer may not automatically include provisions to protect against possible damage from shaft currents. One should at least un­derstand what the manufacturer offers before selection is made.

Other considerations
Mechanical Torsional Consider­ation. In many applications, system mechanical resonances (in the motor, coupling, or driven equipment) may be excited by the harmonics induced in the motor by the VFD.  Many system torsional resonances have tradition­ally been in the 8-25 Hz range and may be excited by the drive when the output frequency is below 20 Hz. As a general rule, when a standard mo­tor is to be operated below 33% of its normal constant frequency speed for an extended period of time, a review of the mechanical (torsional) system is recommended.
Standard vertical induction motor designs often run above the first lateral, critical speed (reed frequency) in con­stant speed applications. This means that the adjustable speed drive may cause the mechanical system to operate at or near a resonance (below the con­stant speed rpm) for extended periods of time and may result in mechanical damage. For this reason, it is neces­sary to always review the mechanical system for vertical induction motors applied in adjustable speed drives.

Electrical Torsional Consider­ations. The VFD may, due to electrical resonances, produce excessive tor­sional oscillations which can lead to mechanical problems. High electrical currents due to electrical resonanc­es may exist at certain frequencies because of the combination of capaci­tances and inductances in the drive and motor electrical system.

Electrical filters in the system should include series resistors to pro­vide damping, or drive operation at these frequencies should be avoided to prevent excessive motor heating and torsional stress.

Bearing Speed Limits. For given sizes of bearings, manufacturers pub­lish limiting speeds. Operation above these speeds should not be considered without research from, and possible substitution by, the bearing manufac­turer.

Lubrication Limits. For rolling ele­ment bearings, common greases using mineral oil may not be appropriate for higher speeds, and often asking a supposed grease “authority” may not yield good information. A good start­ing point is to determine the “speed factor,” which is mean diameter in millimeters times the maximum speed in rpm.  Consider alternative lubricants when the speed factor is above 350,000.  

Estimating size equivalent applied to VFDs
To estimate the equivalent 60 Hz hp rating and size for induction mo­tors applied to VFDs, you can use the following formulae to estimate the size and equivalent 60 Hz rating as well as the stator current at the base speed point of operation. (For 50 Hz, substitute “50” for “60” in the formulae shown below.)

Horsepower calculation.


Where:    hp60 is the equivalent HP rating at 60 Hz
                hpBS is the horsepower rat­ing at Base Speed
                HzBS is the frequency in hertz at Base Speed
                %OLBS  is the overload requirement in %, at Base Speed, minimum value 175
60 Hz example:
                hpBS = 120
                HzBS = 45
                %OLBS = 175

hp60 = 120 x (60/45) x (175/175) = 160

The next higher rating at the 60 Hz speed should be used to determine the motor frame size.
Current calculation. (For 50 Hz, use appropriate voltage values.)
    

Where:    hpBS is the horsepower rat­ing at Base Speed
                Eff60 is the standard motor efficiency at the equivalent 
                60 Hz rating, expressed as a decimal
                PF60 is the standard motor power factor at the equivalent 
                60 Hz rating, expressed as a decimal
                Volts is the rated motor voltage (575, 460, etc.)
Example continued from above:

AmpBS = (120x746)/(0.941 x 0.915) x 1/(460 x 1.732) x 1.15 = 150.01

Note:  When operation at a frequency above the normal line power line frequency is required, the equations above select a higher horsepower.  This higher hp accounts for the reduction in magnetic field to operate successfully at the higher end of the speed range, since the frequency must increase while the voltage should not exceed the machine’s rated voltage. This is no longer a “standard” motor. 



Rate this article:
No rating
Print


PREVIOUS ITEM

Getting The Most From Your Electric Motors

Getting The Most From Your Electric Motors - coverThis 40-page booklet provides great advice for obtaining the longest, most efficient and cost-effective operation from general and definite purpose electric motors.

This booklet covers topics such as:

  • Installation, startup and baseline information
  • Operational monitoring and maintenance
  • Motor and baseline installation data
  • How to read a motor nameplate
  • Motor storage recommendations

LEARN MORE AND DOWNLOAD MÁS INFORMACIÓN Y DESCARGAR BUY PRINTED COPIES

READ MORE ABOUT THE FEATURES AND BENEFITS

EASA/AEMT Rewind Study

EASA Rewind Study cover

The Effect of Repair/Rewinding on Premium Efficiency/IE3 Motors
Tests prove Premium Efficiency/IE3 Motors can be rewound without degrading efficiency.

DOWNLOAD THE FULL RESULTS

ANSI/EASA AR100-2020

ANSI/EASA AR100-2015 cover

Recommended Practice for the Repair of Rotating Electrical Apparatus
This is a must-have guide to the repair of rotating electrical machines. Its purpose is to establish recommended practices in each step of the rotating electrical apparatus rewinding and rebuilding processes.

DOWNLOAD - ENGLISH

DESCARGAR - ESPAÑOL

EASA Technical Manual

EASA Technical Manual cover

Revised May 2024
The EASA Technical Manual is the association's definitive and most complete publication. It's available FREE to members in an online format. Members can also download PDFs of the entire manual or individual sections.

VIEW & DOWNLOAD