Identifying Transient Voltage Events That Can Cause Premature Motor Failure - Private Webinars - EASA | The Electro•Mechanical Authority
Facebook Twitter LinkedIn YouTube Menu Search Arrow Right Arrow Left Arrow Down Arrow Up Home Arrow Next Arrow Previous RSS Icon Calendar Icon Warning Icon

How to schedule

To schedule private education for your group, contact:

Dale Shuter, CMP
Meetings & Expositions Manager

+1 314 993 2220, ext. 3335
dshuter@easa.com

1 hour of training

$300 for EASA Chapters/Regions
$400 for member companies
$800 for non-members

How a webinar works

All EASA private webinars are live events in which the audio and video are streamed to your computer over the Internet. Prior to the program, you will receive a web link to join the meeting. 

The presentation portion of the webinar will last about 45 minutes, followed by about 15 minutes of questions and answers.

Requirements

  • Internet connection
  • Computer with audio input (microphone) and audio output (speakers) appropriate for your size group
  • TV or projector/screen

Zoom logo

The Zoom webinar service EASA uses will ask to install a small plugin. Your computer must be configured to allow this in order to have full functionality. Please check with your IT department or company's security policy prior to scheduling a private webinar.

Private Webinars

EASA's private webinars are an inexpensive way to bring an EASA engineer into your service center, place of business or group meeting without incurring travel expenses or lost production time.

Convention presentation

Identifying Transient Voltage Events That Can Cause Premature Motor Failure

  • June 2011
  • Number of views: 25
  • Article rating:

Chuck Yung
Senior Technical Support Specialist
Electrical Apparatus Service Association

Repairers often face the challenge of determining the cause of motor failures without complete information from the motor user. This paper explores methods to differentiate between damage caused by lightning and other transient conditions such as inadequate ground fault protection or multiple start attempts after an initial failure. Transient conditions, rapid bus transfer, and ungrounded systems can mislead repairers into attributing motor failures to lightning. Other transient events include re-closure, improperly located power factor correction capacitors, accidental connection of a new dual-voltage motor to the wrong voltage, and lightning. Correctly identifying the root cause of a winding fault and using appropriate protection can prevent repeat failures, saving downtime costs that often exceed the motor cost.

The paper discusses lightning arrestors and surge protection, emphasizing proper selection and installation. It includes meteorological sites that plot lightning strikes in North America and root cause failure analysis techniques for evaluating winding failures. Electrical stresses, ranging from low-voltage turn stresses to high-speed, high-voltage transients, can lead to insulation breakdown. Mechanical, thermal, and environmental stresses also contribute to insulation system degradation. Differentiating between cause and effect in winding failures associated with electrical stress can be challenging, often requiring systematic elimination of other possible explanations.

Transient voltages, defined as unexpected changes in voltage, can be destructive to electrical equipment, causing premature failures such as turn-to-turn shorts or turn-to-ground faults. These voltages can reach up to 3.5 times their normal peak values with extremely short rise times. Various sources of transient voltages include repetitive striking, rapid restrike (bus transfer), opening and closing of circuit breakers, capacitor switching, current limiting fuses, partial discharge (corona), and lightning. Each source has unique characteristics that can lead to motor winding damage.

Partial discharge occurs when the voltage is high enough to break down pockets of air within the insulation, causing arcing and releasing ozone that chemically attacks the insulation. This is most destructive when coils are loosely fitted in the slots. Machines rated over 6 kV typically use gradient tape to control partial discharge. Lightning can cause voltage surges through direct contact or induction, with surges propagating along the line. Variable-frequency drives can also introduce voltage spikes during starting and stopping.

Post-mortem analysis is crucial for identifying the root cause of motor failures. Analysts must avoid preconceived ideas and let the evidence guide the investigation. Effective methodologies include the Five Why Methodology, fishbone diagrams, 8D Problem Solving Process, statistical analysis, and Failure Mode Effects Analysis (FMEA). Proper documentation and photo evidence are essential for thorough analysis.

Surge and lightning arrestors should be used to protect motors susceptible to lightning damage. The leads should be as short as possible with minimal bends to reduce impedance. The paper provides guidance on arrestor selection based on system voltage and grounding configuration.

Key Points Covered:

  • Differentiating between lightning damage and other transient conditions
  • Importance of correct root cause identification to prevent repeat failures
  • Electrical stresses and their impact on insulation systems
  • Sources and characteristics of transient voltages
  • Partial discharge and its destructive effects
  • Post-mortem analysis techniques for motor failures
  • Selection and installation of surge and lightning arrestors

Key Takeaways:

  • Accurate identification of motor failure causes is crucial for effective protection and prevention of repeat failures.
  • Transient voltages can significantly reduce winding life and cause premature motor failures.
  • Systematic analysis and elimination of other possible causes are necessary to isolate the electrical stress responsible for the failure.
  • Proper surge and lightning protection can mitigate the risk of damage from transient voltage events.