Facebook Twitter LinkedIn YouTube Menu Search Arrow Right Arrow Left Arrow Down Arrow Up Home Arrow Next Arrow Previous RSS Icon Calendar Icon Warning Icon

Filter the results

  • Enter one or more words to find resources containing any of the words entered
  • Enter words or phrases between " " to find exact match

Resource Library

Article

Power factor: What it is, why it's important

  • January 2002
  • Number of views: 3127
  • Article rating: No rating

Cyndi Nyberg 
Former EASA Technical Support Specialist 

Power factor can be best explained with a short illustration. Figure 1 below shows the three ele­ments to consider. First, true power, measured in kW, is the power that does useful work. Reactive power, measured in kVAR, is the power that is stored and returned by all inductive machines, such as motors and transformers. The apparent power, measured in kVA, is the voltage multiplied by the current in the system. Even though the true power is doing the work, the power company has to dis­tribute the apparent power. 

Image

Mathematically, the power factor is the cosine of the angle between the true and apparent power. Power factor is defined as the ratio of true power used in an electric circuit to the apparent power, or the power that is apparently being drawn from the source. In a sense, apparent power is “bor­rowed” from the power company. Since AC power is continuously reversing, the borrowed power is sent back to the system every time the al­ternating current reverses. 

In electric motors, power factor varies with load (although not directly). A motor running without a load will have a very low power factor, whereas at full load, the power factor may be relatively high. 

A facility that has a very low power factor in the total system may be charged a penalty by the power company for “borrowing” the power without fully using it. This is because more current is being transmitted than is actually doing any useful work. 

Power factor correction 
There are two common methods of correcting plant power factor. One is the use of synchronous motors. Typically, motor inductance causes the current to lag the voltage by a certain angle, the one between true power and apparent power. An ideal situation would not have the current lagging, and therefore the angle between them would be zero, resulting in a unity power factor. Using a synchronous motor in the system will provide power where the current is leading the voltage by a certain angle. This “oppo­site” power can offset the lagging current that is already present, increasing the total system power factor. A synchronous motor can be adjusted to leading power by increasing the excitation voltage to the rotating fields. Use of synchronous motors can be an expensive alternative if a new motor must be purchased (there aren’t any already in the system), but in certain applications may be the best choice. 

Power factor correction capacitors (PFCC’s) are the second method to increase overall system power factor. Figure 2 below shows the typical placement of PFCC’s in the system. When the ca­pacitors are located at position 2, no changes are required for the overloads. However, if the PFCC’s are located at position 3, the current through the overloads will be lower, so the relay must be rated lower to protect the motor. 

Image

It is possible to calculate the drop in amperes as a result of adding the capacitors. You need to know the original power factor and the corrected power factor. Then, using the following equation: 
old PF
% current drop (A) = 100 x (1 - old PF )
                                                  new PF 
For example, suppose that the system power factor was originally 78%, and you improve it to 90%. The percent drop in motor current is: 
% drop= 100 x (1-.78/.90) 
= 100 x (1-.87) 
= 13% drop in current 
For applications like elevators, multispeeds, jogging applications, or starting methods such as wye-delta, part winding, or auto-transformer, the PFCC’s must be placed in position 1. In this case, the power factor shouldn’t be corrected above 95% to prevent over-excitation. 

Sizing Ccapacitors 
Table 1 at right shows the appropriate capaci­tor rating (kVAR) based on the original power factor and the desired power factor after improve­ment. The selected multiplier is applied to either the entire kW load in the system, or to the indi­vidual kW load of a motor. The kW multiplied by the multiplier gives the appropriate kVAR rating of the capacitor. 

Warning for power factor correction 
When power factor correction capacitors are used on an induction motor, the kVAR value of the capacitor should not approach or rise above the power factor above unity. Over-correction can cause over-excitation, causing damage to the motor or the driven equipment in the form of high tran­sient currents, voltages, or torque. 

Note: Power factor correction capacitors pose a potential hazard if they are not properly dis­charged before they are touched. This is true for any power circuit capacitors, such as surge ca­pacitors and starting capacitors. 

Image



Rate this article:
No rating
Print


PREVIOUS ITEM

Getting The Most From Your Electric Motors

Getting The Most From Your Electric Motors - coverThis 40-page booklet provides great advice for obtaining the longest, most efficient and cost-effective operation from general and definite purpose electric motors.

This booklet covers topics such as:

  • Installation, startup and baseline information
  • Operational monitoring and maintenance
  • Motor and baseline installation data
  • How to read a motor nameplate
  • Motor storage recommendations

LEARN MORE AND DOWNLOAD MÁS INFORMACIÓN Y DESCARGAR BUY PRINTED COPIES

READ MORE ABOUT THE FEATURES AND BENEFITS

EASA/AEMT Rewind Study

EASA Rewind Study cover

The Effect of Repair/Rewinding on Premium Efficiency/IE3 Motors
Tests prove Premium Efficiency/IE3 Motors can be rewound without degrading efficiency.

DOWNLOAD THE FULL RESULTS

ANSI/EASA AR100-2020

ANSI/EASA AR100-2015 cover

Recommended Practice for the Repair of Rotating Electrical Apparatus
This is a must-have guide to the repair of rotating electrical machines. Its purpose is to establish recommended practices in each step of the rotating electrical apparatus rewinding and rebuilding processes.

DOWNLOAD - ENGLISH

DESCARGAR - ESPAÑOL

EASA Technical Manual

EASA Technical Manual cover

Revised May 2024
The EASA Technical Manual is the association's definitive and most complete publication. It's available FREE to members in an online format. Members can also download PDFs of the entire manual or individual sections.

VIEW & DOWNLOAD